What is the AC power regulation unit “XP Paracon” commissioning mode?

Answer

The trial run mode is a function that temporarily cancels the thyristor element error detection because a thyristor element error (error code: E03) may be detected due to insufficient load current flow when a trial run is performed without using an actual load. (7 seg display zero -> small zero) In addition, when the AC power regulation unit power is turned on again, the trial run mode is canceled.

2021.6.28:Control equipment for electric heaters in increasing demand for a decarbonized society, AC power regulation unit

2022.3.15:FAQ, what is heater temperature control?